Pre-Pack Integrated
Pre-Action System

Model

EUROSAFE Pre-Pack is a pre-assembled Pre-Action System enclosed in cabinet. Pre-action systems are designed for water sensitive areas that require protection from inadvertent water flow into the sprinkler system piping. Eurosafe Pre-Pack system comes with grooved ends to provide minimum installation time. It comes in a compact, space saving, self-standing cabinet while providing an aesthetically pleasing appearance.

Features

Technical Data

Specification Details
Size 50, 80, 100, 150 & 200 NB
Deluge Valve Model ES0201, UL Listed
Riser Check Valve Model CH
Water Motor Gong Bell UL Listed (Optional supply)
Maximum Working Pressure 17.5 kg/sq.cm (250 psi)
System End Connection Grooved – Standard supply Flanged – Optional supply
Release Panel POTTER, UL Listed (Optional)
Water Flow Switch POTTER, UL Listed
Low Pressure Alarm Switch POTTER, UL Listed
Solenoid Valve Normally closed, 24 VDC, UL Listed
Manual System Shut Off Valve Butterfly Valve, UL Listed (With Tamper Switch)
Automatic Air Supply Oil Less Riser Mounted Compressor (Optional)
Type Single Interlock – Wet Pilot Single Interlock – Dry Pilot Single Interlock – Electric Double Interlock – Electric/Pneumatic Double Interlock – Electric/Electric
Cabinet 14 SWG, Red Finish (RAL 3001)
Approval UL Listed
Scroll to Top